Superpack 960Wh 12.8V 75Ah LiFePO4 Battery Pack For UPS Backup Power
Our Superpack 12.8V 75Ah LiFePO4 battery offers reliable UPS backup for servers, edge IT cabinets,
CCTV, telecom base stations and industrial equipment, and fits solar street lights, RV and off-grid
power systems.
Brand:
SuperpackItem NO.:
SPF12V75Ah-SMProduct Origin:
ChinaColor:
BlackLead Time:
25-30 Working DaysFAQ – Superpack 12.8V 75Ah LiFePO4 UPS Battery
Q1: Does this battery last longer than lead-acid batteries?
A: Yes. It has an 8–10 year service life, versus only 3–5 years for VRLA lead-acid batteries, cutting replacement costs.
Q2: Is this lithium battery cost-efficient in long-term use?
A: It delivers lower total cost of ownership. Longer lifespan, maintenance-free use and less cooling consumption save your overall operation cost.
Q3: Is this battery compact for small server rooms?
A: Yes. It is 40%–60% smaller and lighter than lead-acid batteries of the same capacity, suitable for data centers and
edge IT cabinets.
Q4: How long does it take to fully recharge the battery?
A: It only takes 1–2 hours to full charge, while lead-acid batteries need 8-16 hours. The UPS can get back to standby quickly after power recovery.
Q5: Why choose LiFePO4 for UPS backup power?
A: LiFePO4 features excellent thermal safety and thousands of charge cycles, making it the most stable and reliable lithium solution for UPS systems.
| Item | General Parameter | Remark |
| Rated Capacity | 75Ah |
Standard discharge 0.2C after standard charge 0.2C |
| Minimum Capacity | 71.25Ah | |
| Nominal Voltage | 12.8V | |
| Life Expectation |
Higher than 80% of the Initial Capacity of the battery |
1)Charge:CC@0.2C to 14.6V, then CV till current to 0.05C |
|
Discharge cut-off voltage |
10V~10.8V |
Recommended load cut-off voltage >11.2V |
| Charge cut-off voltage | 14.4V~14.6V | |
|
Cell and assembly method |
IFR32140-15Ah | 4S5P |
| Housing material | SPCC | Spray black |
| Standard charge |
0.2C constant current (CC) charge to 14.6V then constant voltage (CV) 14.6V charge till charge current decline to ≤0.05C |
Charge time : Approx 7h |
| Standard discharge |
Constant current 0.2C, Cut-off voltage 10.8V |
|
|
Maximum Charge Current |
20A@25±3℃ | ≤20A(recommend) |
|
Maximum Continuous Discharge Current |
20A@25±3℃ |
25A <2min |
|
Operation Temperature Range |
Charge : 0~55℃ |
60±25% R.H. |
|
Discharge : -20~60℃ (cell surface temperature≤80℃)
|
||
|
Storage Temperature Range |
Less than 6 months : 0~25℃(SOC≥50%) |
60±25% R.H. |
|
Less than 3 months:-20~35℃(SOC≥50%) |
||
| Approx. Weight | 8.8±0.3kg | |
| Internal resistance | ≤40mΩ | 1KHz,AC |
| Dimension | L*W*H=(240*120*180)±2mm | |
| Terminals | XT60H-F,Female connector, yellow |
UL1015 10AWG 500±10mm |
| Series and parallel | Maximum 4 parallel | |
| IP Rating | IP54 | |
| Communication | RS485 isolated |